[. . . ] We recommend using the Climbox 2 programme and the cooling/heating floor kit, both of which are available in option. [. . . ] In cooling mode, the unit starts as soon as the ambient temperature goes above P09. The ambient box tumbwheel and the outside temperature have no influence on this mode. To install the manual reset thermostat on the unit, you must : 1 - dismount the unit roofing and withdraw the electrical panel door. 2 - fix the 63° C manual reset thermostat on the electrical panel (position 1, next to the 78° C thermostat of the electrical auxiliary devices) 4 - fix the thermostat capillary on the water depar ture copper tube with 2 plastic clips, then cover with the insulation also held in place with 2 plastic clips. Carte électronique / Electronic card / Elektronische Karte Câble téléphonique de 3 x 0, 22 mm2 3 x 0, 22 mm2 telephone cable Telefonkabel 3x0, 22mm2 Bornier J1 Terminal box J1 Klemmleiste J1 Bornier J4 Terminal box J4 Klemmleiste J4 Bornier J5 Terminal box J5 Klemmleiste J5 To modify the parameters below, the unit must be unlocked (see MRS5. If the temperature control is dependent on the outdoor temperature (P03=1), remember to set the control slope (water rule) using parameters P27, P28, P29 and P35. [. . . ] With the thought of material improvement always in mind, CIAT reserves the right, without notice, to proceed with any technical modification. [. . . ]