[. . . ] I01E-EN-01 USER'S MANUAL Programmable Controller Option Board Models 3G3MV-P10CDT-E and 3G3MV-P10CDT3-E (For SYSDRIVE 3G3MV Multi-function Compact Inverters) 3G3MV-P10CDT PLC Option Unit User's Manual Revised June 2003 Notice: OMRON products are manufactured for use according to proper procedures by a qualified operator and only for the purposes described in this manual. The following conventions are used to indicate and classify precautions in this manual. Failure to heed precautions can result in injury to people or damage to the product. DANGER Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury. Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury. [. . . ] Use a proper Connecting Cable (CPM2C-CN111, CS1W-CN114, CS1W-CN118, or CS1W-CN226). Note a) A CQM1H-PRO01-E Programming Console can be connected directly to the PLC. b) A C200H-PRO27-E Programming Console can be connected directly to the PLC with a CS1W-CN224/CN624 Connecting Cable. c) Use a CPM2C-CN111 or CS1W-CN114 Connecting Cable to connect to the communications port as a peripheral port. The communications port can be used simultaneously as both a peripheral port and RS-232C port by using the CPM2C-CN111 Connecting Cable. d) Use a CPM2C-CN111, CS1W-CN118 or CS1W-CN226 Connecting Cable to connect to the communications port as a RS-232C port. 27 Unit Components and Specifications SECTION 2 The communications port can be used simultaneously as both a peripheral port and RS-232C port by using the CPM2C-CN111 Connecting Cable Note The peripheral port and RS-422/485 port cannot be used simultaneously. When using the peripheral port disconnect any devices connected to the RS422/485 port. Communications switch Switch to select port 1 type of connected device Position Communication port 1 OFF (default) ON 7. Programming Console RS-422/485 communication RS-422/485 port (3G3MV-P10CDT3-E only) Used to connect to host computers, or standard external devices. Terminal Arrangement Receive data (input) Send data (output) RDA- RDB+ Shield SDA- SDB+ Connector: Phoenix MSTB 2. 5/5-STF-5. 08AU Note The maximum line length is 500 m. Note The peripheral port and RS-422/485 port cannot be used simultaneously. When using the peripheral port disconnect any devices connected to the RS422/485 port. RS-422/485 switch (3G3MV-P10CDT3-E only) Switch to select 4-wire (RS-422) or 2-wire (RS-485) communication Position Status OFF (down) (default) ON (up) 9. 4-wire communications 2-wire communications Terminating Resistance switch (3G3MV-P10CDT3-E only) Position Termination OFF (down) (default) Disabled ON (up) Enabled Set this switch to ON only for double-ended connection to a Host Link network. I/O connector Connects the CPU Unit to external input and output devices. Sinking outputs COM (-) IN0 (A) IN1 (B) IN2 (Z) OUT0 OUT1 OUT2 OUT3 1 2 COM COM 1 2 3 4 5 6 7 8 9 10 11 12 Connector: WAGO 733-112 (wire cross section 0. 08 to 0. 50 mm ) 28 COM 2 IN3 IN4 IN5 Unit Components and Specifications 11. Relay connector SECTION 2 Connects the CPU Unit to an external output devices. Internally connected to pin 3 of the RS422/485 connector and to the shell of the peripheral connector. Enabled 13. Low battery detection switch (3G3MV-P10CDT3-E only) This switch enables or disables the detection of a low-battery error. Position Low-battery detection Error detection enabled Error detection disabled Disabled OFF ON (up) (default) OFF (down) 29 SECTION 3 Installation and Wiring This section provides information on installing and wiring a 3G3MV-P10CDT Unit. Be sure to follow the directions and precautions in this section when installing the 3G3MV-P10CDT in a panel or cabinet and wiring I/O. 3-1 3-2 3-3 3-4 3-5 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35 Connecting I/O Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35 Wiring Communication Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37 Programming Device Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37 31 Installation and Wiring SECTION 3 3-1 Installation WARNING Do not touch the conductive parts such as internal PCBs or terminal blocks WARNING while power is being supplied. Turn ON the input power supply only after mounting the front cover, terminal covers, bottom cover, Operator, and optional items. Not doing so may result in electrical shock, malfunction, or damage to the product. [. . . ] Resets to zero when done Appendix B Default Value 0 0 0 Home_Request : 1=Home is requested. Once finished we can have either 3. 00=1 (Home_OK) or 3. 01=1 (Home_Error). The maximum time to perform home is defined in DM32 Speed_Run_Fwd : In Speed mode (2. 00=0), it generates Run forward of the inverter with 2. 03=1. Speed_Run_Rev : Like 2. 03, but in reverse direction Home_OK : When home is finished and OK, this bit is activated Home_Error : If home is not finished in the defined timeout DM32, then Home_Error appears and the sequence is cancelled. [. . . ]