[. . . ] 10 times each in X, Y, and Z directions 100 m/s2 3 times each in 6 directions on 3 axes Overvoltage Category II, Pollution Degree 2 EN61010-1 EN61326 Industrial applications
Operating resistance Reset resistance Response time Cable length Control output Indicators Ambient temperature Ambient humidity Elevation Insulation resistance Dielectric strength Vibration resistance Shock resistance Installation environment Safety standards EMC
2
Conductive Level Controller 61F-D21T-V1
Cat. N149-E1-03A
Connections
Operation Diagram
PWR E2-E3 E1-E3 A2 OFF RY:SW1 ON E3 E2 E1 14 E1 E2 E3 11
Wiring Diagram
24 VAC/DC 100-240 VAC A1
Control 12 output
Automatic Water Supply and Drainage Control
1. Drainage (RY-SW1 ON)
P
Pump OFF Pump ON
E1
Indicator OFF
E1
Indicator ON
Pump ON
E2 E3
Indicator ON
E2 E3
Indicator OFF
P Pump OFF
The pump stops when the water level reaches E1 (indicator OFF) and starts when the water level drops below E2 (indicator ON).
The pump starts when the water level reaches E1 (indicator ON) and stops when the water level drops below E2 (indicator OFF).
Cat. N149-E1-03A
Conductive Level Controller
61F-D21T-V1
3
Nomenclature
Front DIP Switch Settings
ON
OFF
Operating resistance knob Power indicator Relay status indicator Operating time knob
SW1 SW2 SW3 SW4
DIP switch
: OFF
: ON SW 4321
NOT USED NOT USED NOT USED
Indicators
Item Power indicator (PWR: Green) Meaning Lit when power is being supplied.
OFF ON
Relay status indicator (RY: Yellow) Lit when relay is operating.
DIP Switch Functions
SWITCH ON
4
ON
Setting Knobs
Item Operating resistance knob Operating time knob Usage Used to set the operating resistance to 10 to 100 k. [. . . ] · If the thickness of a mounting panel is not adequate, or a mistake has been made during installation, the product may become disconnected. Recommended torque: 0. 49 N·m Assured torque: 0. 59 N·m · When using the product, ensure that the wiring is correct before turning on the power. · Use a power-supply voltage that is within the range of specifications. · Use the control source and power supply or power lines that provide inputs with appropriate specifications. · Do not install near heat-generating devices (coils, or devices that use coils). Double-check materials such as connection charts and circuit diagrams. · If electrodes make contact with liquid, purchase and use a separator to prevent such contact. · Keep appropriate distance from devices that generate highfrequency noise (e. g. , high-frequency welders, electronic sewing machines). · Use SELV power supply with over load protection function for DC power supply. The insulation of SELV power supply must be a double or reinforced between input and output. Recommended power supply: type S8VS-06024@ (OMRON made)
Precautions for Correct Use
For Proper Use
1. Make sure to use setting values appropriate for the controlled object. Failure to do so can cause unintended operation, and may result in accident or corruption of the product. Only use this product within a board whose structure allows no possibility for fire to escape. To avoid damage to the exterior of the product, do not use organic solvents (thinner, benzene) or agents with strong alkalinity or acidity.
About Installation
1. (If you do not secure space for heat dissipation, life cycle of the product will be compromised. )
Noise Countermeasures
1. Do not install the product near devices generating strong high frequency waves or surges. When using a noise filter, check the voltage and current and install it as close to the product as possible. [. . . ] IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR. Application Considerations SUITABILITY FOR USE OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customer's application or use of the products. Take all necessary steps to determine the suitability of the product for the systems, machines, and equipment with which it will be used. NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM. [. . . ]