[. . . ] 03_NVspec_ver304e
Version3. 04 2003. 02. 05
AIR CONDITIONER INTERFACE
LM ADAPTER
MODEL: LMAP03U-E
Network Variables Specification
1 2 3 4 5 6 Specification Object Details SNVT Table Network Variables Configuration Properties Node Object P. 2 - 3 P. 4 - 9 P. 10 - 13 P. 14 - 35 P. 36 - 48 P. 49
Appendix A: Fahrenheit conversion of Centigrade data
ProgramID: 9-000A2-0076-0003-03 XIF: 0303lm30. xif
*1. LONWORKS® , and the Echelon logo are trademarks of Echelon Corporation registered in the United States and other countries. *4. XIF is of operation check settled in LonMaker for Windows 3. 0(SP2).
MITSUBISHI ELECTRIC
MITSUBISHI ELECTRIC CORPORATION AIR-CONDITIONING & REFRIGERATION SYSTEMS WORKS
WSN02-2124
-1-
03_NVspec_ver304e
1. Specification
1-1. Object Model
These specifications apply to the communication interface used to connect the LonWorks network and the Mitsubishi Electric M-NET compatible products.
<Model name> 1. Split-type air conditioners Mr. SLIM
NOTE:A-M Converter(PAC-SF48MA-E) is necessary.
3. Heat recovery ventilators LOSSNAY
NOTE:LOSSNAY Adapter(PZ-53ADF-E) is necessary.
1-2. Explanation of Function Setting
This product requires a function setting switch because of the connected model, system configuration and control functions.
SW NO. [. . . ] If an error occurs in an outdoor unit, the indoor unit will also stop with an error. Thus, the error will be output from all indoor units in the same refrigerant system. (However indoor units under stopping are excluded. )
Valid Range
0255 = Error Unit Address 65, 535 = Normal *The value is 0 while LM ADAPTER is initialized.
When Transmitted
This variable is transmitted promptly as the state changes. This variable is also transmitted as the state changes by the operation from the local side such as a local remote controller. This variable is output by the ncilnitStartTm (Initialize Start Time) at the powering of LM ADAPTER.
Update Rate
The maximum update rate is not available.
Default Service Type
Acknowledged NOTE: 1: The release of the indoor unit nvoErrAdrs_n(Error Unit Address) results in the "Off" command of the nviOnOff_n (Request On/Off). For the nvoErrAdrs_n(Error Unit Address) when the indoor unit is under stopping, transmit "Off", after transmitting "On". 2: The error is not output when the indoor unit is stopped, so always use together with the local remote controller or system controller.
WSN02-2124
- 26 -
03_NVspec_ver304e
26n Thermo On/Off state_1
network output SNVT_state nvoThermo_n; This output network variable indicates the On/Off state of the indoor unit , the thermostat and the auxiliary heater for heating. This variable is used to calculate the electric charge.
Valid Range
bit[2] bit[1] 0 1 bit[0] 0 1 status Indoor OFF Indoor ON Indoor thermostat OFF Indoor thermostat ON Supplementary heater OFF Supplementary heater ON
0 1 *The value is 0 while LM ADAPTER is initialized.
When Transmitted
This variable is transmitted promptly when the state changes. This variable is output by the ncilnitStartTm (Initialize Start Time) at the powering of LM ADAPTER.
Update Rate
The value designated by nciMinOutTm (Minimum Send Time) is valid.
Default Service Type
Acknowledged NOTE: This output value is not the addition value or proportional division value of electric charge. It is necessary to perform addition and proportional division based on this output value.
26n Thermo On/Off state 2
network output SNVT_switch nvoThermo_n; This output network variable indicates the On/Off state of the indoor unit. This variable is used to calculate the electric charge.
Valid Range
Thermostat State Indoor thermostat OFF SW1-7OFF state 0 value 0 0 state 0 1 SW1-7O value 0 100%
Indoor thermostat ON 1 *The value is 0 while LM ADAPTER is initialized.
When Transmitted
This variable is transmitted promptly when the state changes. This variable is output by the ncilnitStartTm (Initialize Start Time) at the powering of LM ADAPTER.
Update Rate
The value designated by nciMinOutTm (Minimum Send Time) is valid.
Default Service Type
Acknowledged NOTE: This output value is not the addition value or proportional division value of electric charge. It is necessary to perform addition and proportional division based on this output value. WSN02-2124 - 27 -
03_NVspec_ver304e
28n Model Code
network output SNVT_count nvoIcMdlSize_n; This output network variable indicates the model code that indicates the indoor unit. This variable is used to calculate the electric charge.
Valid Range
065, 534 *The value is 0 while LM ADAPTER is initialized.
When Transmitted
This variable is transmitted promptly when the state changes. Monitoring with a Poll request or Fetch request is required.
Update Rate
The maximum update rate is not available.
Default Service Type
Acknowledged
WSN02-2124
- 28 -
03_NVspec_ver304e
29n Group number
network output SNVT_count nvoGroupNo_n; This output network variable indicates the group number of the indoor unit.
Valid Range
050 *The value is 0 while LM ADAPTER is initialized.
When Transmitted
This variable is transmitted promptly when the state changes. Monitoring with a Poll request or Fetch request is required.
Update Rate
The maximum update rate is not available.
Default Service Type
Acknowledged NOTE: The group number set up by the system controller is outputted.
WSN02-2124
- 29 -
03_NVspec_ver304e
1 Request All Off
network input SNVT_switch nviAllOff; This input network variable is used for the emergency Off of the indoor unit and all ventilation. Under the output of "Emergency OFF" of nvoAllOff cannot operate from other remote controller , system controller. The ON/OFF input for each indoor unit from the master system will be ignored. The emergency stop valid time is set with nciEffectTm_1 (Effective time 1). The indoor unit will not start even if the emergency stop is cancelled.
Valid Range
SW1-7OFF state emergency OFF 0 value not used state 0 SW1-7O value not used 0
1 (*1) *1:The setting to state=0x02-0xFE is interpreted as state=0x01. *This operation is not carried out when there are inputs other than the above. [. . . ] *2:The setting to over 100% is interpreted as 100%.
Default Value
0(All switches) NOTE: It is possible to use with an "ME" remote controller.
WSN02-2124
- 46 -
03_NVspec_ver304e 37
Local Display_1
network input config SNVT_switch nciRmDsp_1; This configuration property defines the presence of the automatic actual operation mode display on the local remote controller. The value is set according to nviRmLck (Request Simplified Locking) and nviRmLim (Request Limit Temperature Setting Range).
Valid Range
Display display no display SW1-7OFF state 0 else value not used state 0 SW1-7O value not used
not used 1 (*1) 0 1 not used 1 (*1) 0. 5% - 100% (*2) *1:The setting to state=0x02-0xFE is interpreted as state=0x01. *2:The setting to over 100% is interpreted as 100%.
Default Value
0(display) NOTE: It is possible to use with an "ME" remote controller. 38
Local Display_2
network input config SNVT_switch nciRmDsp_2; This configuration property defines the presence of the automatic actual operation mode display on the local remote controller. [. . . ]