TJERNLUND PRODUCTS, INC.
1601 Ninth Street · White Bear Lake, MN 55110-6794 PHONE (651) 426-2993 · (800) 255-4208 · FAX (651) 426-9547 Visit our web site · www. tjernlund. com
INCLUDES NEW UC1 UNIVERSAL CONTROL
MODEL SS2 INSTALLATION INSTRUCTIONS
!Recognize this symbol as an indication of important safety information!
OWNER INSTRUCTIONS, DO NOT DESTROY
!CAUTION: The owner of the SS2 must keep the area around the vent terminal free of snow, ice and debris.
NOTE: MAXIMUM FLUE GAS TEMPERATURES MUST NOT EXCEED 650oF (343O C) MINIMUM TEMPERATURE MUST BE 250O F (121O C) AT VENT SYSTEM INLET.
THESE INSTRUCTIONS ARE INTENDED AS AN AID TO QUALIFIED, LICENSED SERVICE PERSONNEL FOR PROPER INSTALLATION, ADJUSTMENT AND OPERATION OF THIS UNIT. READ THESE INSTRUCTIONS THOROUGHLY BEFORE ATTEMPTING INSTALLATION OR OPERATION. [. . . ] Connect #4 on UC1 terminal block to burner motor wire removed from R7184. 12
XL XN
SIDESHOT WITH INTEGRAL UC1 UNIVERSAL CONTROL CONNECTED WITH AN AQUASTAT
AQUASTAT L1 L2 C1 C2 B1 B2 J2
UNIVERSAL CONTROLLER
IMPORTANT: RED JUMPER POSITION MUST BE THE SAME AS APPLIANCE INTERLOCK VOLTAGE. 115V DRY 24V
CALL JUMPER
N J1 L1 LINE VOLTAGE OIL BURNER PRIMARY CONTROL, BURNER RELAY OR GAS VALVE SUPPLY 115 VAC 50/60 Hz
R
IMPORTANT: CRIMP GROUND WIRE TO GROUNDING SPADE TERMINAL IN SS2 ELECTRICAL BOX. CAUTION: WHEN INTERLOCKING WITH AQUASTAT DO NOT DISCONNECT BURNER MOTOR FROM PRIMARY CONTROL / CAD CELL RELAY.
1. Disconnect B1 from L1 of oil burner primary control, burner relay or hot of gas valve and reconnect to #1 on UC1 terminal block. Connect #4 on UC1 terminal block to the L1 on line voltage oil burner primary control, burner relay or gas valve. NOTE: If burner primary control goes out on lockout, the SideShot will continue to run as long as a call for heat is present.
SIDESHOT WITH INTEGRAL UC1 UNIVERSAL CONTROL CONNECTED WITH A CARLIN 40200, 42230, 48245, 50200, 60200 SERIES OR EQUIV. AND A LINE VOLTAGE THERMOSTAT OR AQUASTAT
SUPPLY 115 VAC 60 Hz T Red/White Low Voltage Jumper T Black
XL XN
LEGEND: 115 VAC
D/N 9183046-7
Line Voltage Thermostat or Aquastat Control
Limit IMPORTANT: RED JUMPER POSITION MUST BE THE SAME AS APPLIANCE INTERLOCK VOLTAGE.
F
White 10 FLA / 60 LRA 115V
F
Orange
DRY
24V
BURNER MOTOR A Alarm A Violet 0. 3 A, AC OIL VALVE J1 Blue 500 VA IGNITION TRANS J2
CALL JUMPER
UNIVERSAL CONTROLLER
SUPPLY 115 VAC 50/60 Hz
R
IMPORTANT: CRIMP GROUND WIRE TO GROUNDING SPADE TERMINAL IN SS2 ELECTRICAL BOX.
1. Connect burner motor terminal Orange of Carlin to #1 on UC1 terminal block. Connect #4 on UC1 terminal block to burner motor wire removed from Orange of Carlin. 13
XL XN
LEGEND: 115 VAC
D/N 9183046-3
SIDESHOT WITH INTEGRAL UC1 UNIVERSAL CONTROL CONNECTED WITH A HONEYWELL R8184 SERIES OR EQUIVALENT PRIMARY CONTROL AND A BURNER MOTOR POST-PURGE
L1 THERMOSTAT BLACK ORANGE WHITE B O W T T F 115V DRY 24V F HONEYWELL R8184 SERIES OR EQUIVALENT J2 J1
UNIVERSAL CONTROLLER
IMPORTANT: RED JUMPER POSITION MUST BE THE SAME AS APPLIANCE INTERLOCK VOLTAGE.
CALL JUMPER
OIL VALVE SUPPLY 115 VAC 50/60 Hz
R
XL XN N M MTR
9183006 TJERNLUND PRODUCTS, INC.
LEGEND: 115 VAC
D/N 9183046-4
BURNER MOTOR
IGNITION TRANS
SS2 MOTOR
SS2 COOLING FAN
IMPORTANT: CRIMP GROUND WIRE TO GROUNDING SPADE TERMINAL IN SS2 ELECTRICAL BOX.
1. Separate the burner motor wire and ignition transformer from the Orange wire of R8184. Connect the HOT wire of oil solenoid valve to #4 on UC1 terminal block and neutral wire to White or N. Connect burner motor and ignition transformer HOT wires to M terminal on UC1 and neutrals to White or N. Make sure RED voltage jumper on UC1 is on 115V.
SIDESHOT WITH INTEGRAL UC1 UNIVERSAL CONTROL CONNECTED WITH A SINGLE ZONE 24 VAC THERMOSTAT
IMPORTANT: RED JUMPER POSITION MUST BE THE SAME AS APPLIANCE INTERLOCK VOLTAGE.
THERMOSTAT
Y R G R C J1 Y W INTERNAL CONTROL OF FURNACE SUPPLY 115 VAC 50/60 Hz
R
115V
DRY
24V
W G J2 XL XN
UNIVERSAL CONTROLLER
CALL JUMPER
LEGEND: 115 VAC 24 VAC
D/N 9183046-5
IMPORTANT: CRIMP GROUND WIRE TO GROUNDING SPADE TERMINAL IN SS2 ELECTRICAL BOX.
1. Connect #2 on UC1 terminal block to C on internal control terminal strip of furnace/boiler. Connect #4 on UC1 terminal block to W on internal control terminal strip of furnace/boiler. 14
SIDESHOT WITH INTEGRAL UC1 CONTROL CONNECTED WITH A 24 VAC ELECTRONIC IGNITION MODULE
IMPORTANT: RED JUMPER POSITION MUST BE THE SAME AS APPLIANCE INTERLOCK VOLTAGE. SPARK (9) (8) J2
OR
115V
UNIVERSAL CONTROLLER
DRY
CALL JUMPER
24V
J1
(7) 24V 24V GND BNR GND PV MV / PV MV (6) (5) (4) (3) (2) (1)
PI YE
GR YE WH OR WH OR YE
SUPPLY 115 VAC 50/60 Hz
R
XL XN
LEGEND: 115 VAC 24 VAC
D/N 9183046-8
PV PV MV MV
HONEYWELL IGNITION CONTROL
GR
IMPORTANT: CRIMP GROUND WIRE TO GROUNDING SPADE TERMINAL IN SS2 ELECTRICAL BOX.
GAS VALVE
1. Remove the wire on MV at gas valve and connect it on #1 on UC1 terminal block. Make sure RED voltage jumper on UC1 is on 24V.
SIDESHOT WITH INTEGRAL UC1 UNIVERSAL CONTROL CONNECTED WITH A 24 OR 115 VAC STANDING PILOT
IMPORTANT: RED JUMPER POSITION MUST BE THE SAME AS APPLIANCE INTERLOCK VOLTAGE.
INTERNAL CONTROLS OF FURNACE/BOILER B2 COM Aquastat T-stat B1 HOT 115V
DRY
CALL JUMPER J2 J1
UNIVERSAL CONTROLLER
24V
COM TR
HOT TH
SUPPLY 115 VAC 50/60 Hz
XL XN
LEGEND: 115 VAC 24 OR 115 VAC
D/N 9183046-1
24V OR 115V GAS VALVE IMPORTANT: CRIMP GROUND WIRE TO GROUNDING SPADE TERMINAL IN SS2 ELECTRICAL BOX.
1. Remove the wire on TH or HOT of gas valve and connect it on #1 on UC1 terminal block. [. . . ] Name and address of installer and any service agency who performed work on Power Venter. Date of original installation and dates any service work was performed. warrants the components of the SideShot for two years from date of installation. This warranty does not cover normal maintenance, transportation or installation charges for replacement parts or any other service calls or repairs. [. . . ]