[. . . ] Switch Mode Power Supply
S8VM (15/30/50/100/150/300/600/1, 500-W Models)
Power Supply Featuring OMRON's Unique, New Undervoltage Alarm Function with Compact Body Contributing to Machine Downsizing
· New undervoltage alarm function assists in determining causes of errors (S8VM-· Power failure alarm function provides notification of output voltage errors (300-, 600-, and 1, 500-W models only). · Broad range of possibilities with 8 capacities and 29 models to choose from. 213, EN50178, EN60950-1 (The 300-, 600-, and 1, 500-W models will not conform to safety standards if the customer replaces the fan. ) · Harmonic current emissions: Conforms to EN61000-3-2 (except for 15- and 30-W models). [. . . ] DC output monitor pin (+V) Remote sensing pin (+S) DC output monitor pin (-V) Remote sensing pin (-S) Current balance pin (CB) Signal ground pin for current balance (CBG) 7: Remote control pin (+RC) 8: Remote control pin (-RC) 9: No connect 10: No connect 11: Power failure alarm output pin (PF-C) (collector) 12: Power failure alarm output pin (PF-E) (emitter)
3 4 5 6
7
600-W Models
S8VM-600C
Signal I/O connector (See note 1: 3. ) 2: 3: 4: 2 1 5: 6: 4 3
6 8 10 12 CN
5 7 9 11
1, 500-W Model
S8VM-15224C
Note: 1. Protective earthing connection is the panel mounting hole of the metal case. (A protective earthing connection stipulated in safety standards is used. The enclosed standard connector for signal I/O is mounted to CN when S8VM is shipped. The enclosed signal I/O connector shorts between 1 and 2, between 3 and 4, and between 7 and 8. Do not connect a load to the output voltage monitor terminals (+V, -V).
Output Color Label
This color label identifies the output voltage by color.
Green: Blue: Yellow: White:
Color label identifying output voltage
5V 12 V 15 V 24 V
Note: A 300-W model is shown above. The label is in a different place on 600-W models and 1, 500-W model.
14
Switch Mode Power Supply S8VM
Engineering Data (300-W, 600-W, 1, 500-W Models)
Derating Curve
300W/600W/1, 500W
Load ratio (%)
120 100
Upside-down Mounting (S8VM-15224C Only) Correct
80
1, 500 W
Side Mounting Incorrect
*1
60
Incorrect
Incorrect
40
20
0 -20
-10
0
10
20
30
40
50
60
70 80
Ambient temperature (°C)
Note: 1. Do not use the Power Supply in areas outside the derating curves (i. e. , the area shown by shading A in the above graph). When mounting two or more Power Supplies side-by-side, allow at least 20 mm spacing between them. Always provide at least 50 mm of mounting space for the surface with the fan mounted. C) or 100 mm (S8VM-15224C) of mounting space on the opposite side of the surface with the fan mounted. When using the 1, 500-W model for a long period of time at an input voltage of 90 VAC or lower, reduce the load to 80% or less of the above derating curve. The ambient temperature is specified at a location 50 mm in front of the center of the Power Supply's front panel.
300 W
600 W
1, 500 W
Note: 1. The internal parts may occasionally deteriorate or be broken due to adverse heat dissipation depending on the mounting status. Do not use the Power Supply in any mounting direction other than those specified. To ensure sufficient cooling, do not cover the air holes located on the side the fan is mounted and the opposite side. Mounting screw tightening torque (recommended value: M4 (1. 27 N·m)) The screws must not protrude more than 6 mm inside the Power Supply.
Remote Sensing Function
This function is used to compensate for voltage drops on the load lines. Connect the +S pin (pin 2 on CN) to the positive load terminal and the -S pin (pin 4 on CN) to the negative load terminal to enable remote sensing. When not using the remote sensing function, use the standard connector. The +S and +V pins (pin 1 on CN) and the -S and -V pins (pin 3 on CN) will be connected.
+V S8VM CN -V -S *1 *2 +
Mounting
Standard Mounting Correct Correct Correct
300 W
*1
600 W
*1
1, 500 W
*1
+V +S -V
Horizontal Mounting Correct Correct Correct Note: 1. Use as thick a wire as possible since high voltage drops on the load lines (* 2) may activate the overvoltage protection function. [. . . ] ADJ).
Note: Expected fan service life Exhaust temperature 45°C: 45, 000 hours Exhaust temperature 80°C: 11, 000 hours
The Power Supply will not conform to safety standards if the customer replaces the fan.
Buzzing Noise when the Input Is Turned ON
50/100/150/300/600/1, 500-W Models
A harmonic current suppression circuit is built into the input power. This circuit can create noise when the input is turned ON, but it will last only until internal operation stabilizes and does not indicate any problem in the Power Supply.
300/600/1, 500-W Models
The possible cause for no output voltage may be that the overcurrent protection, overvoltage protection, or overheat protection has operated. Alternatively, the built-in fan may have stopped or the remote control function may be OFF. If there is no output voltage even after checking the following points, please contact your OMRON representative.
DIN Rail Mounting
15/30/50/100/150/300/600-W Models
When mounting to a DIN Rail, lower the S8VM onto the Rail until the Rail stopper clicks into place, hook section A over the edge of the Rail and push in the direction of B.
Check the overload protected status.
Check whether the load is in overload status or is short-circuited. [. . . ]