If this document matches the user guide, instructions manual or user manual, feature sets, schematics you are looking for, download it now. Diplodocs provides you a fast and easy access to the user manual SAUNIER DUVAL THEMA CLASSIC F24E PLUS. We hope that this SAUNIER DUVAL THEMA CLASSIC F24E PLUS user guide will be useful to you.
Manual abstract: user guide SAUNIER DUVAL THEMA CLASSIC F24E PLUS
Detailed instructions for use are in the User's Guide.
[. . . ] 4000121771-2. 02. 03
Instructions for Use Installation and Servicing
To be left with the user
Themaclassic F24E PLUS
Fanned Flue Combination Boiler G. C. No. 47-920-37
Themaclassic F30E PLUS
Fanned Flue System Boiler G. C. No. 47-920-38
Hepworth Heating Ltd. , Nottingham Road, Belper, Derbyshire. DE56 1JT
Guarantee Registration
Thank you for installing a new Saunier Duval appliance in your home. [. . . ] H - Screws . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . I - 'O' rings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . J
70mm 184mm 65mm
Note : Top of boiler casing not front panel
Horizontal Top flue kit
Diagram 12a. 1
Diagram 12a. 2
4000121771-2
24
11886
12a. 1 The Horizontal Top flue - kit 86285
12 Horizontal Top Flue Installation
Outside wall face L Flue centre line C L 90mm
11643
4000121771-2
12a. 4 Installation of horizontal top flue assembly
Important: If the flue has been cut, ensure that there are no burrs that could damage the `O' ring. · Remove the backing from the self adhesive gasket (H) and carefully fit gasket to base of elbow (C). · Fit both `O' rings (J) into the flue elbow (C), one at the inlet, one at the outlet. By necessity, they are a loose fit, apply a small amount of suitable lubricant to each `O' ring when fitting. · Fit rubber sealing collar (F), into groove at the outer end of pipe (A). · Insert flue duct pipe (B) into inner end of air duct pipe (A), rotate flue duct pipe to locate into groove inside air duct pipe. · Fit air/flue duct pipe assembly through the wall with rubber sealing collar to the outside. · Fit the fixing collar seal (D) onto the flue duct pipe (B) ensuring it is the correct way round (the larger diameter onto the pipe). · Pull air/flue duct pipe assembly inwards to bring rubber sealing collar (F) hard up against external wall. Carefully push the fixing collar seal onto the elbow ensuring that the flue duct pipe locates into the flue elbow outlet while taking care not to tear the `O' ring. · Fit the fixing collar (E) around the fixing collar seal (D) and secure with 2 screws provided. · Push the internal plastic flange (G) along the air duct pipe (A) until engaged against internal wall.
17mm Air duct cutting length L minus 90mm plus 17mm = cutting length Flue duct Air duct
Flue duct cutting length Air duct cutting length + 95mm = cutting length
25mm check dimension (cut end)
Diagram 12a. 3
25
13 Electrical Connection
WARNING: This appliance must be earthed. Any fault arising from incorrect wiring cannot be put right under the terms of the Saunier Duval guarantee. Electrical components have been tested to meet the equivalent requirements of the BEAB. Connection of the whole electrical system and any heating system controls to the electrical supply must be through a common isolator. Isolation should preferably be by a double pole switched fused spur box having a minimum contact separation of 3mm on each pole. The fused spur box should be readily accessible and preferably adjacent to the boiler. A fused three pin plug and shuttered socket outlet may be used instead of a fused spur box provided that: a) They are not used in a room containing a fixed bath or shower. b) Both the plug and socket comply with the current issue of BS1363.
13. 1 Mains Cable
Important: If a replacement supply cable is required it must be purchased. S1008600.
13. 2 Voltage Free External Controls
WARNING: UNDER NO CIRCUMSTANCES MUST ANY MAINS VOLTAGE BE APPLIED TO ANY OF THE TERMINALS ON THE VOLTAGE FREE HEATING CONTROLS CONNECTION TERMINAL. [. . . ] · Pull out slotted metal clip from valve body and remove valve.
10017
Diagram 20. 21 Diagram 20. 23
9767
DISCHARGE PIPE
11925
Diagram 20. 24
11398
THREE WAY VALVE ACTUATOR
IGNITION UNIT
Diagram 20. 22
4000121771-2
9785
DOMESTIC SAFETY VALVE (10 BAR BLUE)
52
11597
THREE WAY VALVE/ BYPASS HOUSING
11596
DOMESTIC HOT WATER PLATE TO PLATE HEAT EXCHANGER
20 Replacement of Parts
20. 36 Micro accumulator vessel thermistor, refer to diagram 20. 25.
Before starting refer to the front of Section 20 Important information. · Locate micro accumulator vessel thermistor, on top of the micro accumulation vessel. · Disconnect the inline electrical connection plug to the micro accumulator vessel thermistor. · Release the micro accumulator vessel heating element cable from the securing clips, note the routing of the cable for reassembly. [. . . ]