5824 Serial/Parallel Interface Gateway Module Installation Instructions
The 5824 Serial/Parallel Interface Gateway Module (5824) connects a Silent Knight fire alarm control panel (FACP) directly to a printer to print event history. [. . . ] Remove knockout if running wires through the back of the base, and mount the base using any of the mounting holes provided (Figure 2). Mounting hardware not included.
Compatibility
The 5824 is compatible with all Silent Knight addressable FACPs and with the 5208 conventional FACP.
Mounting
The 5824 has a plastic enclosure that is surface mounted.
To mount the 5824 enclosure:
1. Remove the 5824 circuit board from the enclosure base by pushing outward on one of the snap retaining tabs at the bottom (as
Figure 2: Enclosure Base
P/N 151392
5824 Serial/Parallel Interface Gateway Module Installation Instructions
4. Snap the circuit board back in the base so the snap retaining tabs hold it in place.
Note: It may be necessary to wire to the circuit board before placing it back in the base. See Wiring to a FACP.
Table 2: ID Dip Switch Settings ID Number 0* 1 2 3 4 5 6 7 8 Switches 1 Down Up Down Up Down Up Down Up Down 2 Down Down Up Up Down Down Up Up Down Up = On 3 Down Down Down Down Up Up Up Up Down Down = Off 4 Down Down Down Down Down Down Down Down Up
Wiring to a FACP
See Table 1 and Figure 3 to terminate the wiring.
Table 1: 5824 to FACP Connections 5824 Terminals B A S+ SFACP SBUS Terminals B A + - (or GND)
* Zero is not used.
Connecting to a Printer
Connect the printer cable to the serial or parallel on the 5824 and then connect it to the printer. Printer cable not included.
Figure 3: Wiring the 5824 to the FACP
Setting DIP Switches
Each module on a Silent Knight FACP requires an ID number which is set using the DIP switches on the 5824 circuit board. [. . . ] See the FACP installation manual for specific information on device ID assignments.